GAS 210 ECO PRO
24
114494-190310
The boiler has several control, protection and regulation connec-
tion options. The standard control PCB (PCU-01) can for example
be expanded with:
an optional 0 - 10 V control PCB (available as an accessory IF-01);
and/or the optional expanded control/protection PCB (available as
an accessory SCU-SO1).
To install or access these PCBs, the plastic cap must be removed
from the control panel. The required external connections are
made on these (optional) PCBs. The various connection options
are detailed in the following sections.
8.3.1 Connection options of standard control unit
(PCU-01)
Connected on the standard control unit (PCU-01) is the safety unit
(SU) connected, which protects the boiler.
Mainson/of
N
NL
Pump
L
OT BL RL
OT BL RL
X6
X1
X11
X10
X9
X7
X8
X2
X3
X5
X4
F1 1.6 AT
PCU-01
SU
NL
Pump
X9X11 X10
1
4x
2
114492LTAL21H005e
fig. 10 Standard control PCB (PCU-01) with
safety unit (SU)
8.3.2 On/off control (OT)
The boiler is suitable for connection to a ‘volt free’ on/off controller.
Connect the controller to the On/off - OT terminals of terminal
strip X6 (not polarity sensitive).
8.3.3 Modulating controls (OT)
The boiler is set up for communication via the OpenTherm proto-
col. Modulating controllers can be connected.
Connection is made with a two-core cable to the On/off - OT ter-
minals of terminal strip X6 (it does not matter which wire is con-
nected to which cable clamp).
8.3.4 External interlock (BL)
The boiler has an external interlock switch, so that the boiler can
be shutdown in the event that this switch is not made. This input
can be used in combination with a flue gas thermostat (available
as an accessory). This input relates to the BL terminals of terminal
strip X6. Remove the wire bridge before using the input.
The input's behaviour depends on the parameter 33 setting:
1 = Normal shutdown;
2 = Shutdown without frost-protection (= default);
3 = Lock out.